TB-0911 — DCI® D Concrete – Bond to Reinforcing Steel

/ concrete / mix design

Introduction

It is very important to know whether a material added to concrete increases or decreases the concrete’s bond to reinforcing steel. Flood Testing Laboratories, Inc. Chicago, Illinois was asked in 1990 to study the bond strengths of four concrete mixes containing FORCE 10,000®  D microsilica admixture and/or DCI®  Corrosion Inhibitor to black rebar and epoxy-coated rebar. This Engineering Bulletin will report the effect on bond strength and other mechanical properties of concrete by the addition of FORCE 10,000®  D and DCI®.

Table 1 — Concrete Mix Designs

  MIX A
Reference
MIX B
DCI®
MIX C
FORCE
10,000® D
MIX D
DCI®/FORCE 10,000® D
Cement - Type I – kg/m3 (lb/yd3) 390 (658) 390 (658) 390 (658) 390 (658)
Sand – kg/m3 (lb/yd3) 840 (1,420) 840 (1,420) 840 (1,420) 840 (1,420)
Coarse Aggregate - #57 – kg/m3 (lb/yd3) 1,070 (1,800) 1,070 (1,800) 1,070 (1,800) 1,070 (1,800)
Total Water* – kg/m3 (lb/yd3) 148 (250) 148 (250) 148 (250) 148 (250)
Water/cement-ratio 0.38 0.38 0.38 0.38
FORCE 10,000® D        
L/m3 (gal/yd3) 44.5 (9) 29.6 (6)
microsilica – kg/m3 (lb/yd3) 29.4 (49.5) 19.6 (33.0)
% microsilica/100 kg (100 lbs) 7.5 (7.5) 5.0 (5)
DCI®– L/m3 (gal/yd3) 19.8 (4) — 14.8 (3)
DARACEM® 19 – mL/100 kg (oz/100 lbs) 835 (12.8) 795 (12.2) 725 (11.1) 725 (11.1)
Slump – mm (in.) 150 (6) 150 (6) 150 (6) 150 (6)
Air (%) 2.5 1.8 2.3 2.0
Unit weight – kg/m3 (lb/ft3) 2,435 (152.0) 2,454 (153.2) 2,437 (152.1) 2,437 (152.1)
Compressive Strength – MPa (psi)        
3 days 43.7 (6,345) 46.0 (6,680) 56.8 (8,235) 46.3 (6,720)
7 days 56.1 (8,135) 58.5 (8,485) 65.0 (9,430) 61.7 (8,950)
28 days 64.5 (9,350) 74.5 (10,800) 88.6 (12,850) 76.0 (11,020)
Flexural Strength – MPa (psi)        
3 days 5.24 (760) 5.24 (760) 6.31 (915) 5.10 (740)
7 days 6.41 (930) 6.83 (990) 8.03 (1,165) 6.17 (985)
28 days 7.41 (1,075) 7.64 (1,108) 10.53 (1,528) 9.19 (1,333)

* Total water includes added mix water, aggregate moisture, and Force 10,000® D and DCI®  water.

Table 1 — Concrete Mix Designs

  Standard Uncoated Rebar     Epoxy-Coated Rebar      
Concrete Mixture Bond Strength MPa Bond Strength (psi) Improvement Compared to Mix A (%) Bond Strength MPa Bond Strength (psi) Improvement Compared to Mix A (%) Compared to Standard Rebar Mix A (%)
A 12.1 (1,760) 8.4 (1,213) 68.9
B 12.9 (1,878) 106.7 9.8 (1,425) 117.5 81.0
C 12.7 (1,845) 104.8 8.8 (1,275) 105.1 72.4
D 12.4 (1,808) 102.7 10.6 (1,533) 126.4 87.1

Test Data

The concrete mix design studied is a fairly common mix used for corrosion protection type concretes. The reference mix (Mix A) contains 390 kg/m3 (658 lbs) Type I cement and a water/ cement-ratio of 0.38. All mixture designs tested are shown in Table 1. Mix B contains 19.8 L/m3 (4 gal) of DCI®  per cubic meter (yard). Mix C contains FORCE 10,000®  D at 7.5% microsilica by weight of cement. Mix D includes FORCE 10,000®  D at 5% and DCI®  at 14.8 L (3 gal). The amount of water in all materials was added to maintain a constant total water content. Slump was adjusted to 150 mm (6 in.) with the use of a superplasticizer, DARACEM®  19. The mixtures were not air entrained. Slump, air and unit weight were measured. Compressive and flexural strengths at 3, 7 and 28 days were determined using ASTM C 39 and ASTM C 78 respectively.

Bond strength to the reinforcing steel was determined using ASTM C 234-86 “Comparing Concretes on the Basis of the Bond Developed with Rein-forcing Steel”. Number 6 reinforcing steel was used in concrete specimens 150 mm x 150 mm x 300 mm (6 in. x 6 in. x 12 in.). Tension is applied to the bar in an attempt to pull it out of the concrete specimens. The bond strength in MPa (psi) is recorded throughout the test and that strength reported at a bar slippage of 0.25 mm (0.010 in.) Results of the bond test are reported in Table 2.

Conclusions

  1. The addition of DCI®  and/or FORCE 10,000®  D increased the concrete’s bond to standard uncoated reinforcing steel by an average of 4.7% and to epoxy-coated rebar by an average of 16.3%.
  2. The addition of DCI®  and/or FORCE 10,000®  D increased the compressive and flexural strength of concrete.
  3. There was an average 22.7% reduction in bond strength when epoxy-coated reinforcing steel was used when compared to standard rebar.

 

gcpat.com | North America Customer Service: +1 (877) 423 6491

We hope the information here will be helpful. It is based on data and knowledge considered to be true and accurate and is offered for consideration, investigation and verification by the user, but we do not warrant the results to be obtained. Please read all statements, recommendations and suggestions in conjunction with our conditions of sale, which apply to all goods supplied by us. No statement, recommendation, or suggestion is intended for any use that would infringe any patent, copyright, or other third party right.

DCI®, FORCE, ADVA, DARACEM, DARATARD, DAREX and DARAVAIR are trademarks, which may be registered in the United States and/or other countries, of GCP Applied Technologies Inc. This trademark list has been compiled using available published information as of the publication date and may not accurately reflect current trademark ownership or status. These products may be covered by patents or patents pending.

© Copyright 2018 GCP Applied Technologies Inc. All rights reserved.

.

In Canada, 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6.

GCP0083 TB-0911-0418


GCP Applied Technologies Inc., 2325 Lakeview Parkway, Suite 400, Alpharetta, GA 30009, USA
GCP Canada, Inc., 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6
This document is only current as of the last updated date stated below and is valid only for use in the United States. It is important that you always refer to the currently available information at the URL below to provide the most current product information at the time of use. Additional literature such as Contractor Manuals, Technical Bulletins, Detail Drawings and detailing recommendations and other relevant documents are also available on www.gcpat.com. Information found on other websites must not be relied upon, as they may not be up-to-date or applicable to the conditions in your location and we do not accept any responsibility for their content. If there are any conflicts or if you need more information, please contact GCP Customer Service.

Last Updated: 2023-06-28

https://gcpat.com/en/solutions/products/dci-corrosion-inhibitor/tb-0911-dci-force-10000-d-concrete-bond-reinforcing