TB-0603 — Strength and Durability of Flowing Concrete using DARACEM® 19 Technical Bulletin

Introduction

A series of tests was conducted to evaluate the durability of flowing, superplasticized concrete. Three separate loads of concrete were produced with various addition rates of DARACEM® 19 to produce concrete with slumps ranging from 178 mm to 254 mm (7 in. to 10 in.). Standard tests were performed, including air content, slump and unit weight. Two beams were cast from each mix for freeze-thaw durability analysis (ASTM Method C666, Procedure B, Rapid Freezing in Air and Thawing in Water).

The test results show that DARACEM® 19 provided compressive strengths 2 to 5 MPa (250 to 700 psi) higher than the reference mix even at equal water-cement ratio. Thus, DARACEM® 19 provides a double benefit of increased workability (higher slumps), coupled with higher strengths, at the same cement content. This is due to the greatly improved dispersion of cement provided by the DARACEM® 19. The data also shows relative durability factors 95% and more of the reference mix after 300 freeze-thaw cycles.

Summary

To summarize, flowing concrete can be made which gives an increase in the degree of workability, coupled with higher compressive strengths, as well as proper freeze-thaw durability.

Flowing Concrete with DARACEM® 19, Summary of Test Data

Test Designation A B C
Cement, kg/m3 (lbs/yd3) 335 (564) 335 (564) 335 (564)
Sand, kg/m3 (lbs/yd3) 783 (1320) 783 (1320) 783 (1320)
Coarse agg, kg/m3 (lbs/yd3) 1038 (1750) 1038 (1750) 1038 (1750)
Water, kg/m3 (lbs/yd3) 177 (298) 174 (293) 177 (299)
W/C ratio 0.53 0.52 0.53
Daravair®, mL/m3 (oz/yd3) 155 (4.0) 164 (4.25) 164 (4.25)
       
Before DARACEM® 19      
Air, % 6.0 6.5 7.0
Slump, mm (in.) 121 (4.75) 114 (4.50) 127 (5.00)
Unit weight, kg/m3 (lbs/ft3) 2307 (144.0) 2300 (143.6) 2281 (142.4)
Yield, m3 (ft3) 1.01 (27.31) 1.02 (27.35) 1.02 (27.62)
       
After DARACEM® 19      
Amount of DARACEM® 19 added, mL/100 kg (oz/100 lbs) 0.0 (0.0) 456 (7.0) 652 (10.0)
Air, % N/T 6.2 6.2
Slump, mm (in.) N/T 178 (7.00) 254 (10.00)
Temperature, °C (°F) 24 (76) 26 (79) 26 (78)
Unit weight, kg/m3 (lbs/ft3) N/T 2320 (144.8) 2320 (144.8)
Yield, m3 (ft3) N/T 1.00 (27.12) 1.01 (27.16)
       
Compressive Strength, MPa (psi)      
3 day % of reference 19.5 (2830) 100 23.2 (3370) 119 23.0 (3340) 118
7 day % of reference 24.6 (3570) 100 27.4 (3970) 111 26.4 (3830) 107
28 day % of reference 33.7 (4890) 100 37.2 (5390) 107 37.5 (5440) 109
56 day % of reference 37.7 (5460) 100 40.2 (5830) 107 41.0 (5950) 109
       
Freeze-Thaw Durability      
Durability factor % of reference 98.5 100 95.0 96.0 95.0 96.0

gcpat.com | North America Customer Service: +1 (877) 423 6491

We hope the information here will be helpful. It is based on data and knowledge considered to be true and accurate and is offered for consideration, investigation and verification by the user, but we do not warrant the results to be obtained. Please read all statements, recommendations and suggestions in conjunction with our conditions of sale, which apply to all goods supplied by us. No statement, recommendation, or suggestion is intended for any use that would infringe any patent, copyright, or other third party right.

STRUX is a trademark, which may be registered in the United States and/or other countries, of GCP Applied Technologies Inc. This trademark list has been compiled using available published information as of the publication date and may not accurately reflect current trademark ownership or status.

© Copyright 2018 GCP Applied Technologies Inc. All rights reserved.

.

In Canada, 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6.


GCP Applied Technologies Inc., 2325 Lakeview Parkway, Suite 400, Alpharetta, GA 30009, USA
GCP Canada, Inc., 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6
This document is only current as of the last updated date stated below and is valid only for use in the United States. It is important that you always refer to the currently available information at the URL below to provide the most current product information at the time of use. Additional literature such as Contractor Manuals, Technical Bulletins, Detail Drawings and detailing recommendations and other relevant documents are also available on www.gcpat.com. Information found on other websites must not be relied upon, as they may not be up-to-date or applicable to the conditions in your location and we do not accept any responsibility for their content. If there are any conflicts or if you need more information, please contact GCP Customer Service.

Last Updated: 2023-06-28

https://gcpat.com/en/solutions/products/daracem-mid-range-water-reducer/tb-0603-strength-and-durability-flowing-concrete