PERM-A-BARRIER® Air Barriers NFPA Compliant Wall Assemblies Data Sheet

Special Notes and Alternate Allowances:
Mineral Wool Allowance- NFPA 285 tables for mineral wool are not available. For any listed insulation, mineral wool may be used as a replacement for combustible insulation.
No Insulation Allowance - NFPA 285 tables for no insulation are not available. Where the WRB is allowed over combustible insulation, those WRB’s allowed over the insulation may be used on the base-wall with no insulation.

  • It is not permitted to remove insulation from a table – unless the table allows WRB over the insulation. In this case, when the insulation is removed, then that WRB over the insulation is to be used on the base wall surface.
  • Do not use the WRB as listed on the base wall surface when removing the insulation to allow the WRB over the insulation.
  • Adhere to the maximum air gap as stated within the approval when performing this process.

WRB Allowance - GCP PERM-A-BARRIER® or PERM-A-BARRIER® Ultra may replace any WRB shown since this WRB is less combustible than the WRBs listed in the approvals.
WRBs may not be used under and over insulation. -Where an approval does not list “None” for WRB, None may be used to comply with the point above.
Where an approval does not list air gaps for specific claddings, use the air gap tested for brick (usually 2 inches) as a maximum.

Walls containing up to 3 in. Kingspan GreenGuard® XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

 

Walls containing XPS insulation

Wall ComponentsMaterials
Base Wall System 
Use any of these options
 
1Concrete Wall
2Concrete Masonry Wall
320-gauge (min) 3 5/8 in. depth (min.) steel studs spaced at a maximum of 16 in. o.c. with lateral bracing every 4 ft. vertically
a1 layer - 5/8 in. thick Type X or 1/2 in. thick Type X gypsum wallboard on interior
Floorline Firestopping14 lb/cu ft mineral wool (i.e., Thermafiber®) in each stud cavity at each floor line, attached with Z-clips or equivalent
Cavity Insulation 
Use any of these options
 
1None
2Any noncombustible insulation per ASTM E136
3Fiberglass (Batt type Class A ASTM E84 faced or unfaced
Exterior Sheathing
Use any of these options
1None
2Minimum 1/2 in. thick, exterior type gypsum sheathing
3Minimum 5/8 in. thick, Type X, exterior type gypsum sheathing
Air Barrier or Weather-Resistive Barrier Applied to Exterior Sheathing1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPS
4PERM-A-BARRIER® NPL
5PERM-A-BARRIER® Ultra
NoteAll WRB to be installed at the indicated or recommended application rates and per the manufacturer installation instructions
Exterior Insulation1Kingspan GreenGuard® XPS - 1/2 in. minimum and 3 in. maximum
NoteSeal all insulation joints with maximum 4 in. wide asphalt or Butyl based flashing tape 
Exterior Veneer
Use any of these options
 
1Brick
 
aStandard nominal 4 in. thick, clay brick
bBrick veneer anchors - standard types - installed maximum 24 in. o.c. vertically on each stud
cMaximum 2 in. air gap between exterior insulation and brick
2Concrete
aMinimum 2 in. thick
bMaximum 2 in. air gap between exterior insulation and concrete.
3CMU - Concrete Masonry Units 
aMinimum 4 in. thick
bMaximum 2 in. air gap between exterior insulation and CMU
4Stone Veneer
aMinimum 2 in. thick limestone or natural stone veneer
bMinimum 1 1/2 in. thick cast artificial stone veneer
cAny standard non-open joint technique may be used (such as shiplap, etc.)
5Terracotta Cladding
aMinimum 1 1/4 in. thick
bAny standard joint installation technique may be used (such as shiplap, etc.)
6Portland cement-sand plaster (Stucco) over metal lath
aMinimum 3/4 in. thick
b2 or 3-coat application
cNo air gap between Stucco veneer and exterior insulation

Walls containing up to 4 in. Kingspan GreenGuard® XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

Wall ComponentsMaterials
Base Wall System 118-gauge 3 5/8 in. depth (min.) galvanized steel studs spaced at a maximum 24 in. o.c.
a1 layer - 5/8 in. thick gypsum wallboard on interior
Cavity Insulation 1Unfaced fiberglass batt insulation
Exterior Sheathing1One (1) layer 1/2 in. thick exterior type gypsum
Air Barrier or Weather-Resistive Barrier Applied to Exterior Sheathing
Use any of these options
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® Ultra
Exterior Insulation1Kingspan GreenGuard® XPS Insulation Board- 4 in. thickness
WRB Over Exterior Insulation110mm Keene Building Products Driwall™ Rainscreen drainage mat
Exterior Veneer1Glen-Gery Thin Veneer Brick
aFirst a layer of 1/2 in. thick PermaBASE® cement board
bLaticrete MVIS™ Thin Brick Mortar applied to full surface of PermaBASE®
cThin Veneer Brick applied with Glen-Gery Mortar Blend Portland cement-line mortar as grout

Walls containing Dow Styrofoam™ XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

Wall ComponentMaterials
Base Wall System 
Use either 1, 2, 3, or 4
 
1Concrete Wall
2Concrete Masonry Unit (CMU) Wall
3Steel studs: minimum 3 5/8 in. depth, minimum 20-gauge at a maximum spacing of 24 in. OC. One layer of 5/8 in. thick Type X gypsum wallboard on interior face of studs. Gypsum wallboard joints shall receive at a minimum a LeveI 2 finish with all fasteners covered with joint compound.
4Wood studs: Minimum 2-inch x 4-inch FRTW wood studs spaced at a maximum of 24-inch OC. One layer of 5/8 in. thick Type X gypsum wallboard installed on interior face of wood studs. One layer of 5/8 in. thick Type X exterior gypsum sheathing installed on exterior face of wood studs. Minimum two top plates at floorlines. As an option, any thickness of plywood or OSB may be installed on exterior face of wood studs under exterior gypsum sheathing.
Floorline Firestopping
Required in curtain-wall construction
 
4 lb/cu ft mineral wool friction fit in each stud cavity, at each floorline
Stud Cavity Insulation 
Use either 1, 2, 3, or 4
 
1None
2Fiberglass batt insulation (faced or unfaced)
3Mineral wool blown-in or batt insulation (faced or unfaced)
4Any noncombustible material
Exterior Sheathing
Use either 1, 2, 3, or 4
 
15/8 in. thick Type X glass mat gypsum sheathing
21/2 in. thick glass mat gypsum sheathing
35/8 in. thick DensElement® sheathing - The joints of the DensElement® sheathing may be sealed with R-Guard FastFlash Liquid Flashing or approved equivalent
NoteExterior sheathing is optional for Base wall systems 1 and 2 above
WRB Materials Applied to Exterior  Sheathing 
Use either 1, 2, 3, 4, or 5
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® Ultra
NoteAny WRB shown above can be applied over Base Wall System 1 or 2 above, where able.
Continuous insulation adhesive
Use either 1, 2, 3, or 4
 
1None
2Sto TurboStick Adhesive
3Sto ExtraSeal®
4DuPont™ Insta Stik™ quick set polyurethane adhesive
Continuous insulationDuPont™ Styrofoam™ Type IV per ASTM C578. Total thickness to be minimum 1/2 in. to maximum 3 in. XPS products include the Blue Styrofoam™, Grey Styrofoam™ (covered in ICC-ESR 2142), and Grey Styrofoam™ brand ST-100 Series (LIMS-274901) Styrofoam™ (covered in ICC-ESR 4755).
Sealing of exterior insulation
Use either 1 or 2
 
1None
2Seal all exterior insulation joints, and as an option, veneer tie penetrations with:
aDuPont™ LiquidArmor™ - CM Flashing and Sealant-max. 50-mil wet thickness, max. 4 in. width
bDuPont™ LiquidArmor™ - LT Flashing and Sealant-max. 35-miI wet thickness, max. 4 in. width.
cAsphalt, acrylic, or butyl-based flashing tape - max. 4 in. width
dDuPont™ Great Stuff PRO™- Use on joints that are ≤ 1/4 in. width, vertical joints must be staggered & remove significant excess from the face of the XPS
Secondary WRB material
Use either 1, 2, or 3
 
1None
2No. 15 Grade D building paper
3Asphalt felt in compliance with ASTM D226
Drainage Mat
Use either 1 or 2
 
1None
2Sto DrainScreen® - installed over Air Barrier and water-resistive barrier membrane or over continuous insulation
Exterior VeneerStucco - Minimum 3/4 in. thick 2 - or 3-coat stucco complying with ASTM C926 applied over 2 1/2 -lb/yd^2 galvanized steel diamond mesh lath complying with ASTM C1063/C847. As an option, adhered masonry veneer, such as: Thin brick, manufactured stone, ceramic or porcelain tile may be installed over the Stucco

gcpat.com | North America Customer Service: +1 (877) 423 6491

We hope the information here will be helpful. It is based on data and knowledge considered to be true and accurate, and is offered for consideration, investigation and verification by the user, but we do not warrant the results to be obtained. Please read all statements, recommendations, and suggestions in conjunction with our conditions of sale, which apply to all goods supplied by us. No statement, recommendation, or suggestion is intended for any use that would infringe any patent, copyright, or other third party right.

GCP Applied Technologies and PERM-A-BARRIER® are trademarks, which may be registered in the United States and/or other countries, of GCP Applied Technologies Inc. This trademark list has been compiled using available published information as of the publication date and may not accurately reflect current trademark ownership or status.

© Copyright 2021 GCP Applied Technologies Inc. All rights reserved. PAB-126-0221


GCP Applied Technologies Inc., 2325 Lakeview Parkway, Suite 400, Alpharetta, GA 30009, USA
GCP Canada, Inc., 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6
This document is only current as of the last updated date stated below and is valid only for use in the United States. It is important that you always refer to the currently available information at the URL below to provide the most current product information at the time of use. Additional literature such as Contractor Manuals, Technical Bulletins, Detail Drawings and detailing recommendations and other relevant documents are also available on www.gcpat.com. Information found on other websites must not be relied upon, as they may not be up-to-date or applicable to the conditions in your location and we do not accept any responsibility for their content. If there are any conflicts or if you need more information, please contact GCP Customer Service.

Last Updated: 2026-06-08