PERM-A-BARRIER® Air Barriers NFPA Compliant Wall Assemblies Data Sheet

Special Notes and Alternate Allowances:
Mineral Wool Allowance- NFPA 285 tables for mineral wool are not available. For any listed insulation, mineral wool may be used as a replacement for combustible insulation.
No Insulation Allowance - NFPA 285 tables for no insulation are not available. Where the WRB is allowed over combustible insulation, those WRB’s allowed over the insulation may be used on the base-wall with no insulation.

  • It is not permitted to remove insulation from a table – unless the table allows WRB over the insulation. In this case, when the insulation is removed, then that WRB over the insulation is to be used on the base wall surface.
  • Do not use the WRB as listed on the base wall surface when removing the insulation to allow the WRB over the insulation.
  • Adhere to the maximum air gap as stated within the approval when performing this process.

WRB Allowance - GCP PERM-A-BARRIER® or PERM-A-BARRIER® Ultra may replace any WRB shown since this WRB is less combustible than the WRBs listed in the approvals.
WRBs may not be used under and over insulation. -Where an approval does not list “None” for WRB, None may be used to comply with the point above.
Where an approval does not list air gaps for specific claddings, use the air gap tested for brick (usually 2 inches) as a maximum.

Walls containing up to 3 in. Kingspan GreenGuard® XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

 

Walls containing XPS insulation
Wall ComponentsMaterials
Base Wall System 
Use any of these options
 
1Concrete Wall
2Concrete Masonry Wall
320-gauge (min) 3 5/8 in. depth (min.) steel studs spaced at a maximum of 16 in. o.c. with lateral bracing every 4 ft. vertically
a1 layer - 5/8 in. thick Type X or 1/2 in. thick Type X gypsum wallboard on interior
Floorline Firestopping14 lb/cu ft mineral wool (i.e., Thermafiber®) in each stud cavity at each floor line, attached with Z-clips or equivalent
Cavity Insulation 
Use any of these options
 
1None
2Any noncombustible insulation per ASTM E136
3Fiberglass (Batt type Class A ASTM E84 faced or unfaced
Exterior Sheathing
Use any of these options
1None
2Minimum 1/2 in. thick, exterior type gypsum sheathing
3Minimum 5/8 in. thick, Type X, exterior type gypsum sheathing
Air Barrier or Weather-Resistive Barrier Applied to Exterior Sheathing1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPS
4PERM-A-BARRIER® NPL
5PERM-A-BARRIER® Ultra
NoteAll WRB to be installed at the indicated or recommended application rates and per the manufacturer installation instructions
Exterior Insulation1Kingspan GreenGuard® XPS - 1/2 in. minimum and 3 in. maximum
NoteSeal all insulation joints with maximum 4 in. wide asphalt or Butyl based flashing tape 
Exterior Veneer
Use any of these options
 
1Brick
 
aStandard nominal 4 in. thick, clay brick
bBrick veneer anchors - standard types - installed maximum 24 in. o.c. vertically on each stud
cMaximum 2 in. air gap between exterior insulation and brick
2Concrete
aMinimum 2 in. thick
bMaximum 2 in. air gap between exterior insulation and concrete.
3CMU - Concrete Masonry Units 
aMinimum 4 in. thick
bMaximum 2 in. air gap between exterior insulation and CMU
4Stone Veneer
aMinimum 2 in. thick limestone or natural stone veneer
bMinimum 1 1/2 in. thick cast artificial stone veneer
cAny standard non-open joint technique may be used (such as shiplap, etc.)
5Terracotta Cladding
aMinimum 1 1/4 in. thick
bAny standard joint installation technique may be used (such as shiplap, etc.)
6Portland cement-sand plaster (Stucco) over metal lath
aMinimum 3/4 in. thick
b2 or 3-coat application
cNo air gap between Stucco veneer and exterior insulation

Walls containing up to 4 in. Kingspan GreenGuard® XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

Wall ComponentsMaterials
Base Wall System 118-gauge 3 5/8 in. depth (min.) galvanized steel studs spaced at a maximum 24 in. o.c.
a1 layer - 5/8 in. thick gypsum wallboard on interior
Cavity Insulation 1Unfaced fiberglass batt insulation
Exterior Sheathing1One (1) layer 1/2 in. thick exterior type gypsum
Air Barrier or Weather-Resistive Barrier Applied to Exterior Sheathing
Use any of these options
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® Ultra
Exterior Insulation1Kingspan GreenGuard® XPS Insulation Board- 4 in. thickness
WRB Over Exterior Insulation110mm Keene Building Products Driwall™ Rainscreen drainage mat
Exterior Veneer1Glen-Gery Thin Veneer Brick
aFirst a layer of 1/2 in. thick PermaBASE® cement board
bLaticrete MVIS™ Thin Brick Mortar applied to full surface of PermaBASE®
cThin Veneer Brick applied with Glen-Gery Mortar Blend Portland cement-line mortar as grout
Walls containing Dow Styrofoam™ XPS Insulation

Please refer to XPS manufacturers’ recommendations for window and door header details.

Wall ComponentMaterials
Base Wall System 
Use either 1, 2, 3, or 4
 
1Concrete Wall
2Concrete Masonry Unit (CMU) Wall
3Steel studs: minimum 3 5/8 in. depth, minimum 20-gauge at a maximum spacing of 24 in. OC. One layer of 5/8 in. thick Type X gypsum wallboard on interior face of studs. Gypsum wallboard joints shall receive at a minimum a LeveI 2 finish with all fasteners covered with joint compound.
4Wood studs: Minimum 2-inch x 4-inch FRTW wood studs spaced at a maximum of 24-inch OC. One layer of 5/8 in. thick Type X gypsum wallboard installed on interior face of wood studs. One layer of 5/8 in. thick Type X exterior gypsum sheathing installed on exterior face of wood studs. Minimum two top plates at floorlines. As an option, any thickness of plywood or OSB may be installed on exterior face of wood studs under exterior gypsum sheathing.
Floorline Firestopping
Required in curtain-wall construction
 
4 lb/cu ft mineral wool friction fit in each stud cavity, at each floorline
Stud Cavity Insulation 
Use either 1, 2, 3, or 4
 
1None
2Fiberglass batt insulation (faced or unfaced)
3Mineral wool blown-in or batt insulation (faced or unfaced)
4Any noncombustible material
Exterior Sheathing
Use either 1, 2, 3, or 4
 
15/8 in. thick Type X glass mat gypsum sheathing
21/2 in. thick glass mat gypsum sheathing
35/8 in. thick DensElement® sheathing - The joints of the DensElement® sheathing may be sealed with R-Guard FastFlash Liquid Flashing or approved equivalent
NoteExterior sheathing is optional for Base wall systems 1 and 2 above
WRB Materials Applied to Exterior  Sheathing 
Use either 1, 2, 3, 4, or 5
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® Ultra
NoteAny WRB shown above can be applied over Base Wall System 1 or 2 above, where able.
Continuous insulation adhesive
Use either 1, 2, 3, or 4
 
1None
2Sto TurboStick Adhesive
3Sto ExtraSeal®
4DuPont™ Insta Stik™ quick set polyurethane adhesive
Continuous insulationDuPont™ Styrofoam™ Type IV per ASTM C578. Total thickness to be minimum 1/2 in. to maximum 3 in. XPS products include the Blue Styrofoam™, Grey Styrofoam™ (covered in ICC-ESR 2142), and Grey Styrofoam™ brand ST-100 Series (LIMS-274901) Styrofoam™ (covered in ICC-ESR 4755).
Sealing of exterior insulation
Use either 1 or 2
 
1None
2Seal all exterior insulation joints, and as an option, veneer tie penetrations with:
aDuPont™ LiquidArmor™ - CM Flashing and Sealant-max. 50-mil wet thickness, max. 4 in. width
bDuPont™ LiquidArmor™ - LT Flashing and Sealant-max. 35-miI wet thickness, max. 4 in. width.
cAsphalt, acrylic, or butyl-based flashing tape - max. 4 in. width
dDuPont™ Great Stuff PRO™- Use on joints that are ≤ 1/4 in. width, vertical joints must be staggered & remove significant excess from the face of the XPS
Secondary WRB material
Use either 1, 2, or 3
 
1None
2No. 15 Grade D building paper
3Asphalt felt in compliance with ASTM D226
Drainage Mat
Use either 1 or 2
 
1None
2Sto DrainScreen® - installed over Air Barrier and water-resistive barrier membrane or over continuous insulation
Exterior VeneerStucco - Minimum 3/4 in. thick 2 - or 3-coat stucco complying with ASTM C926 applied over 2 1/2 -lb/yd^2 galvanized steel diamond mesh lath complying with ASTM C1063/C847. As an option, adhered masonry veneer, such as: Thin brick, manufactured stone, ceramic or porcelain tile may be installed over the Stucco
Walls containing a maximum 4.25-inch thick ThermaxTM insulation board
Wall ComponentMaterials
Base Wall System 
Use either 1, 2, 3, 4, 5, or 6
 
1Concrete Wall
2Concrete Masonry Unit (CMU) Wall
3Standard clay brick wall
4Adobe block wall
5Wood studs: nominal 2-in. x 4-in. or greater FRTW wood studs spaced at a maximum of 24-in. OC. Wall cavity empty (no insulation) or filled with fiberglass batt insulation (faced or unfaced) or mineral wool insulation (faced or unfaced). One layer of 5/8 in. thick Type X gypsum wallboard installed on interior face of wood studs. One layer of 5/8 in. thick Type X exterior gypsum sheathing installed on exterior face of wood studs. Minimum two top plates at floorlines. As an option, any thickness of plywood or OSB may be installed on exterior face of wood studs under exterior gypsum sheathing.
6Steel studs: minimum 3 5/8 in. depth, minimum 20-gauge at a maximum spacing of 24 in. OC with lateral bracing every 4 ft. vertically with:
aOne layer of 5/8 in. thick Type X gypsum wallboard on interior face of studs. Gypsum wallboard joints shall receive at a minimum a LeveI 2 finish with all fasteners covered with joint compound, or
bMONOKOTE® Z-3306 installed at a minimum 3/8 in. thickness over Thermax, or
cInternational Cellulose Corporation's Ure-K® Thermal Barrier System installed at a minimum of 1 1/4 in. thickness over Thermax
Floorline Firestopping
Required in curtain-wall construction
 
4 lb/cu ft mineral wool (e.g., Thermafiber) in each stud cavity and at each floor line - friction fit cavity, attached with Z-clips, or equivalent
Interior Vapor / Moisture barrier for use with Base Wall 5 or 61None
2Any 6-mil thick polyethylene film
Cavity Insulation 
Use either 1, 2, or 3 or combination of 2 and 3
 
1None - Screw end of fasteners that protrude into the stud cavity can be covered with a maximum of 1 1/2 in. diameter plug of DuPont™ Froth-Pak™ Class A rated per ASTM E84
2Maximum 2 in. thickness of BASF SPRAYTITE® 81206 SPF (covered in Intertek CCRR-1031) or BASF WALLTITE® LWP (covered in Intertek CCRR-0374) applied using sheathing or insulation as
substrate and covering the width of the cavity and inside the stud flange. Must cover the SPRAYTITE® 81206 or WALLTITE® LWP above any window, louver or door opening with minimum 2 in. thickness
of mineral wool insulation (1 1/2 in. mineral wool cover in 3 1.2 in. deep studs). The mineral wool insulation must be installed from top of opening to bottom of floor deck above. Additionally, a special
construction of the header must be used. 
 
Exterior Sheathing
Use either 1, 2, or 3
OR
 
1None
21/2 in. thick exterior gypsum sheathing
35/8 in. thick Type X exterior gypsum sheathing
NoteExterior sheathing is not required for Base wall systems 1 through 4 above
Multi-Function Sheathing & WRB Products1USG Securock® ExoAir® 430 System
NoteThis item replaces the exterior sheathings above. When this item is used the exterior sheathings are not required and WRBs below (Layer IV) shall not be used.
WRB Materials Applied to Exterior Sheathing 2 or 3
Use either 1, 2, 3, 4, 5, 6, or 7
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® NPL 10
6PERM-A-BARRIER® VPL 50 RS
7PERM-A-BARRIER® Ultra
NoteAny WRB material shown above can be applied over Base Wall System 1 through 4 above, where able.
Drainage Mat
Use either 1 or 2
 
1None
2DuPont™ Tyvek® DrainVent™ Rainscreen - Limited to use as:
Must be used in conjunction with any WRB shown above
Exterior veneers #1 thru #6 in Layer VIII below when no air gap is present between the veneer and the DrainVentTM
Exterior veneers #2 thru #15, #16b thru 16m, #17 and #19 in Layer VIII below when no air gap is present between the veneer and the DrainVentTM
 
Exterior Insulation
Use either 1 or 2
 
1None (Exterior sheathing must be Item 2 or 3 listed in exterior sheathings above)
2DuPont ThermaxTM Brand Rigid Insulation - Total thickness to be a minimum of 5/8 in. to maximum of 4 1/4 in.
Exterior Insulation Joint Flashing 
Use either 1 or 2
 
1None - Only when a water-resistive barrier is applied to the exterior sheathing or when a water-resistive barrier is applied to the exterior insulation
2Flash all exterior insulation joints and veneer tie penetrations with one of the following:
aDuPont LiquidArmorTM - CM Flashing and Sealant-max. 60-mil wet thickness, max. 5 in. width
bDuPont LiquidArmorTM - LT Flashing and Sealant-max. 35-miI wet thickness, max. 5 in. width.
cDuPont LiquidArmorTM - QS Flashing and Sealant-max. 60-mil wet thickness, max. 5 in. width
dDuPont Tyvek® Fluid Applied Flashing & Joint Compound -max. 25-mil wet thickness, max. 3 in. width
eDuPont WeatherMateTM Flashing - max. 4 in. width
fAsphalt, acrylic, or butyl-based flashing tape - max. 4 in. width
gDuPont Great Stuff Pro- Use on joints that are ≤ 1/4 in. width, vertical joints must be staggered & remove significant excess from the face of the Thermax
hDOWSIL DEFENDAIRTM 200 or DOWSIL DEFENDAIRTM 200C
NoteWith either e) or f), a small amount of spray primer may be used to aid in adhesion; maximum 4 in. width
Exterior Veneer
Use either 1, 2, 3, 4, 5, or 6
 
1Brick - Standard type brick veneer anchors, installed a maximum of 24-inches OC vertically on each stud. A maximum 2-inch air gap between the exterior insulation and the brick. Use standard nominal 4-inch thick clay bricks.
2Stucco - Minimum 3/4 in. thick, exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier can be 1 or 2 layers of asphalt building paper but shall not be full-coverage asphalt or butyl-based self-adhered membranes.
3Minimum 2 in. thick limestone or natural stone veneer or minimum 1 1/2 in. thick artificial cast stone veneer. Any standard non-open-joint installation technique such as ship-lap, etc., can be used.
4Terracotta cladding - minimum 1 1/4 in. thick terracotta cladding system. Any non-open-joint installation technique such as ship-lap, etc. can be used.
5Concrete or precast concrete panels - Minimum 1 1/2 in. thick panel, with a 2-in. maximum air gap between exterior insulation and concrete panel. Any standard non-open-joint installation technique such as ship-lap, etc. can be used.
6Concrete Masonry Units - Minimum 2 in. thick panel, with a 2 in. maximum air gap between exterior insulation and the interior face of the exterior CMU. Any standard non-open-joint installation technique can be used
Flashing of Window, Door, and Other Exterior Wall PenetrationsAs an option, flash window, door and other exterior penetrations with either.
aDuPont LiquidArmorTM - CM Flashing and Sealant - max. 60-mil wet thickness, max. 12 in. width.
bDuPont LiquidArmorTM - LT Flashing and Sealant - max. 35-mil wet thickness, max. 12 in. width.
cDuPont LiquidArmorTM - QS Flashing and Sealant-max. 60-mil wet thickness, max. 12 in. width
dDuPont Tyvek® Fluid Applied Flashing & Joint Compound -max. 25-mil wet thickness, max. 3 in. width
eDuPont DuraGardTM CM Transition Flashing - max. 12 in. width
fLimited amounts of acrylic, asphalt or butyl-based flashing tape - max. 12 in. width.
gHohmann & Barnard TextroflashTM Flashing
hDOWSIL DEFENDAIRTM 200 or DOWSIL DEFENDAIRTM 200C
NoteFlashing tape used in wall openings may extend the wall width plus extend up to a maximum of 4 in. onto the exterior face of the sheathing. Flashing tape may be used on sheathing exterior corners where the flashing tape may extend a maximum of 4 in. onto the sheathing face on either side of the corner
Mortar NetAs an option, non-full wall coverage mortar drop and drainage nets and meshes can be installed at base of wall and at shelf angles to permit water drainage. Maximum 12 in. high
Walls containing a maximum 3-inch thick ThermaxTM insulation board
Wall ComponentMaterials
Base Wall System 
Use either 1, 2, 3, 4, 5, or 6
 
1Concrete Wall
2Concrete Masonry Unit (CMU) Wall
3Standard clay brick wall
4Adobe block wall
5Wood studs: nominal 2-in. x 4-in. or greater FRTW wood studs spaced at a maximum of 24-in. OC. Wall cavity empty (no insulation) or filled with fiberglass batt insulation (faced or unfaced) or mineral wool insulation (faced or unfaced). One layer of 5/8 in. thick Type X gypsum wallboard installed on interior face of wood studs. One layer of 5/8 in. thick Type X exterior gypsum sheathing installed on exterior face of wood studs. Minimum two top plates at floorlines. As an option, any thickness of plywood or OSB may be installed on exterior face of wood studs under exterior gypsum sheathing.
6Steel studs: minimum 3 5/8 in. depth, minimum 20-gauge at a maximum spacing of 24 in. OC with lateral bracing every 4 ft. vertically with:
aOne layer of 5/8 in. thick Type X gypsum wallboard on interior face of studs. Gypsum wallboard joints shall receive at a minimum a LeveI 2 finish with all fasteners covered with joint compound, or
bMONOKOTE® Z-3306 installed at a minimum 3/8 in. thickness over Thermax, or
cInternational Cellulose Corporation's Ure-K® Thermal Barrier System installed at a minimum of 1 1/4 in. thickness over Thermax
Floorline Firestopping
Required in curtain-wall construction
 
4 lb/cu ft mineral wool (e.g., Thermafiber) in each stud cavity and at each floor line - friction fit cavity, attached with Z-clips, or equivalent
Interior Vapor / Moisture barrier for use with Base Wall 5 or 61None
2Any 6-mil thick polyethylene film
Cavity Insulation 
Use either 1, 2, or 3 or combination of 2 and 3
 
1None - Screw end of fasteners that protrude into the stud cavity can be covered with a maximum of 1 1/2 in. diameter plug of DuPont™ Froth-Pak™ Class A rated per ASTM E84
2Maximum 2 in. thickness of BASF SPRAYTITE® 81206 SPF (covered in Intertek CCRR-1031) or BASF WALLTITE® LWP (covered in Intertek CCRR-0374) applied using sheathing or insulation as
substrate and covering the width of the cavity and inside the stud flange. Must cover the SPRAYTITE® 81206 or WALLTITE® LWP above any window, louver or door opening with minimum 2 in. thickness
of mineral wool insulation (1 1/2 in. mineral wool cover in 3 1.2 in. deep studs). The mineral wool insulation must be installed from top of opening to bottom of floor deck above. Additionally, a special
construction of the header must be used. 
 
3Fiberglass blown-in or batt insulation (faced or unfaced) or mineral wool blown-in or batt insulation (faced or unfaced)
Exterior Sheathing
Use either 1, 2, or 3
OR
 
1None
21/2 in. thick exterior gypsum sheathing
35/8 in. thick Type X exterior gypsum sheathing
NoteExterior sheathing is not required for Base wall systems 1 through 4 above
Multi-Function Sheathing & WRB Products1USG Securock® ExoAir® 430 System
NoteThis item replaces the exterior sheathings above. When this item is used the exterior sheathings are not required and WRBs below (Layer IV) shall not be used.
WRB Materials Applied to Exterior Sheathing 2 or 3
Use either 1, 2, 3, 4, 5, 6, or 7
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® NPL 10
6PERM-A-BARRIER® VPL 50 RS
7PERM-A-BARRIER® Ultra
NoteAny WRB material shown above can be applied over Base Wall System 1 through 4 above, where able.
Drainage Mat
Use either 1 or 2
 
1None
2DuPont™ Tyvek® DrainVent™ Rainscreen - Limited to use as:
 Must be used in conjunction with any WRB shown above
Exterior veneers #1 thru #6 in Layer VIII below when no air gap is present between the veneer and the DrainVentTM
Exterior veneers #2 thru #15, #16b thru 16m, #17 and #19 in Layer VIII below when no air gap is present between the veneer and the DrainVentTM
 
Exterior Insulation
Use either 1 or 2
 
1None (Exterior sheathing must be Item 2 or 3 listed in exterior sheathings above)
2DuPont™ ThermaxTM Brand Rigid Insulation - Total thickness to be a minimum of 5/8 in. to maximum of 3 in.
Exterior Insulation Joint Flashing 
Use either 1 or 2
 
1None - Only when a water-resistive barrier is applied to the exterior sheathing or when a water-resistive barrier is applied to the exterior insulation
2Flash all exterior insulation joints and veneer tie penetrations with one of the following:
aDuPont™ LiquidArmor™ - CM Flashing and Sealant-max. 60-mil wet thickness, max. 5 in. width
bDuPont™ LiquidArmor™ - LT Flashing and Sealant-max. 35-miI wet thickness, max. 5 in. width.
cDuPont™ LiquidArmor™ - QS Flashing and Sealant-max. 60-mil wet thickness, max. 5 in. width
dDuPont™ Tyvek® Fluid Applied Flashing & Joint Compound -max. 25-mil wet thickness, max. 3 in. width
eDuPont™ WeatherMateTM Flashing - max. 4 in. width
fAsphalt, acrylic, or butyl-based flashing tape - max. 4 in. width
gDuPont™ Great Stuff PRO™- Use on joints that are ≤ 1/4 in. width, vertical joints must be staggered & remove significant excess from the face of the Thermax
hDOWSIL DEFENDAIR™ 200 or DOWSIL DEFENDAIR™ 200C
NoteWith either e) or f), a small amount of spray primer may be used to aid in adhesion; maximum 4 in. width
Exterior Veneer
Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18 or 19
 
1ACM System - Use any Aluminum Composite Material (ACM) system that has been successfully tested by the panel manufacturer via the NFPA 285 test method. Acceptable NFPA 285 testing shall consist of successful NFPA test results on a wall assembly incorporating a comparable thickness of combustible foam insulation (e.g., polyiso) behind the ACM. These ACM panel systems include:
-Reynobond® FR ACM
-ALPOLIC® fr ACM
-ALUCOBOND® PLUS ACM
2Terracotta cladding - use any terracotta cladding system in which terracotta is minimum 1 1/4 in. thick. Any standard installation can be used.
3Metal exterior wall coverings such as steel, aluminum, copper, zinc, etc. Any standard installation technique can be used
4Fiber-cement siding (noncombustible) - minimum 1/4 in. thick. Any standard installation technique with noncombustible furring can be used. A maximum 1 1/2 in. air gap allowed behind the fiber-cement siding.
5Brick - Standard nominal 4 in. thick, clay brick with standard type brick veneer anchors, installed maximum 24 in. OC vertically on each stud. Air gap between exterior insulation and brick to be a maximum of 2 in.
6Stucco - Minimum 3/4 in. thick, exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier can be 1 or 2 layers of asphalt building paper but shall not be full-coverage asphalt or butyl-based self-adhered membranes.
7Corium Thin brick system
8Minimum 1 1/4 in. thick limestone or natural stone veneer or minimum 1 1/4 in. thick artificial cast stone veneer. Any standard installation technique such as ship-lap, etc., can be used.
9StoneLite® natural stone wall panels by Stone Panels, Inc.
10Glen-Gery Thin Tech® Elite Series- Masonry veneer
11Concrete or precast concrete panels - Minimum 1 1/2 in. thick panel. Air gap between exterior insulation and concrete panel shall be as per wall design. Any standard installation technique can be used.
12Ceramic tile (min. 3/8 in. thick) bonded using noncombustible mortar adhesive to minimum 1/2 in. thick cement board or gypsum sheathing
13Thin brick (min. 3/4 in. thick clay brick) fully adhered with cementitious mortar (standard or polymer modified} to min. 1/2 in. thick cement backer board or gypsum sheathing. A secondary water-resistive barrier can be installed between the board/sheathing and the brick. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes.
14Natural stone or artificial stone (min. 3/4 in. thick clay brick) fully adhered with cementitious mortar (standard or polymer modified) to min. 1/2 in. thick cement backer board or gypsum sheathing. A secondary water-resistive barrier can be installed between the board/sheathing and the stone. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes
15Concrete Masonry Units - Minimum 2 in. thick panel, with a 2 in. maximum air gap between exterior insulation and the interior face of the exterior CMU. Any standard non-open-joint installation technique can be used
16Knight Wall Systems to include:
aACM System - Use any ACM system that has been successfully tested by the panel manufacturer via the NFPA 285 test method. Any standard installation technique can be used. These ACM panel systems include:
-Reynobond® FR ACM
-ALPOLIC® fr ACM
-ALUCOBOND® PLUS ACM
bTerracotta cladding - use any terracotta cladding system in which terracotta is minimum 1 1/4 in. thick. Any standard installation can be used.
cMetal exterior wall coverings such as steel, aluminum, copper, zinc, etc. Any standard installation technique can be used
dBrick - Standard nominal 4 in. thick, clay brick with standard type brick veneer anchors, installed maximum 2 in. OC vertically on each stud. Air gap between exterior insulation and brick to be as per wall design.
eStucco - Minimum 3/4 in. thick, exterior cement plaster and lath attached to minimum 1/2 in. thick backer board. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier can be 1 or 2 layers of asphalt building paper but shall not be full-coverage asphalt or butyl-based self-adhered membranes.
fCorium Thin brick system
gMinimum 1 1/4 in. thick limestone or natural stone veneer or minimum 1 1/4 in. thick artificial cast stone veneer. Any standard installation technique such as ship-lap, etc., can be used.
hStoneLite® natural stone wall panels by Stone Panels, Inc.
iGlen-Gery Thin Tech® Elite Series- Masonry veneer
jConcrete or precast concrete panels - Minimum 1 1/2 in. thick panel. Air gap between exterior insulation and concrete panel shall be as per wall design. Any standard installation technique can be used.
kCeramic tile (min. 3/8 in. thick) bonded using noncombustible mortar adhesive to minimum 1/2 in. thick cement board or gypsum sheathing
lThin brick (min. 3/4 in. thick clay brick) fully adhered with cementitious mortar (standard or polymer modified} to min. 1/2 in. thick cement backer board or gypsum sheathing. A secondary water-resistive barrier can be installed between the board/sheathing and the brick. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes.
mNatural stone or artificial stone (min. 3/4 in. thick clay brick) fully adhered with cementitious mortar (standard or polymer modified) to min. 1/2 in. thick cement backer board or gypsum sheathing. A secondary water-resistive barrier can be installed between the board/sheathing and the stone. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes
17Cornerstone Building Products to include:
-PBR Panel (Exposed fasteners)
-PBU Panel (Exposed fasteners)
-AVP Panel (Exposed fasteners)
-Designer Series Panels (Exposed fasteners)
-ShadowRib™ Panels (Exposed fasteners)
-NuWall® Panels (Exposed fasteners)
-MasterLine 16® (Concealed fasteners)
18FUNDERMAX Gmbh "M Look" panels - 7-mm thick, installed with 1 to 1 1/2 in. air gap behind the panels and using exposed fasteners.
19TABS II Plus Wall System w/o TABS II Plus "RainScreen" with Pre-attached wrap.
Flashing of Window, Door, and Other Exterior Wall PenetrationsAs an option, flash window, door and other exterior penetrations with either.
aDuPont™ LiquidArmor™ - CM Flashing and Sealant - max. 60-mil wet thickness, max. 12 in. width.
bDuPont™ LiquidArmor™ - LT Flashing and Sealant - max. 35-mil wet thickness, max. 12 in. width.
cDuPont™ LiquidArmor™ - QS Flashing and Sealant-max. 60-mil wet thickness, max. 12 in. width
dDuPont™ Tyvek® Fluid Applied Flashing & Joint Compound -max. 25-mil wet thickness, max. 3 in. width
eLimited amounts of acrylic, asphalt or butyl-based flashing tape - max. 12 in. width.
fHohmann & Barnard Textroflash™ Flashing
gDOWSIL DEFENDAIR™ 200 or DOWSIL DEFENDAIR™ 200C
hDuPont™ DuraGard™ CM Transition Flashing - max. 12 in. width
NoteFlashing tape used in wall openings may extend the wall width plus extend up to a maximum of 4 in. onto the exterior face of the sheathing. Flashing tape may be used on sheathing exterior corners where the flashing tape may extend a maximum of 4 in. onto the sheathing face on either side of the corner
Mortar NetAs an option, non-full wall coverage mortar drop and drainage nets and meshes can be installed at base of wall and at shelf angles to permit water drainage. Maximum 12 in. high
For Firestone (now Amrize) Enverge™ CI foil exterior wall insulation or Enverge™ CI glass exterior wall insulation wall component
Wall ComponentMaterials
Base Wall System 
Use either 1, 2, or 3
 
1Concrete Wall
2Concrete Masonry Wall
31 layer - 5/8 in. thick Type X gypsum wallboard on interior, installed over steel studs: minimum 3 5/8 in. depth, minimum 20-gauge at a maximum of 24 in. OC with lateral bracing every 4 ft. vertically
Floorline Firestopping4 lb/cu ft mineral wool (e.g., Thermafiber®) in each stud cavity and at each floor line - attached with Z-clips or equivalent
Cavity Insulation 
Use either 1, 2, or 3
 
1None
2Any noncombustible insulation
3Fiberglass batt insulation (faced or unfaced)
Exterior Sheathing
Use either 1, 2, or 3
 
1None
21/2 in. thick, exterior type gypsum sheathing
35/8 in. thick, exterior type gypsum sheathing
Water-Resistive Barrier Applied to Exterior Sheathing 2 or 3 above
Use either 1, 2, 3, 4, 5, or 6
 
1PERM-A-BARRIER® Aluminum Wall Membrane
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPL LT
4PERM-A-BARRIER® VPS
5PERM-A-BARRIER® NPL
6PERM-A-BARRIER® Ultra
Exterior Insulation
Use either 1 or 2
 
1Firestone Enverge™ CI Foil Exterior Wall Insulation - 2 1/2 in. maximum thickness with Exterior Veneer - Part 1 or 4 in. maximum thickness with Exterior Veneer - Part 2
2Firestone Enverge™ CI Glass Exterior Wall Insulation - 2 1/2 in. maximum thickness with Exterior Veneer - Part 1 or 4 in. maximum thickness with Exterior Veneer - Part 2
Flashing
Use either None, 1, or 2
 
Optional - Flash all exterior insulation joints and veneer tie penetrations with
14 in. wide Shuretape® AF 100 or AF 975CT aluminum foil tape
2Asphalt or butyl-based flashing tape-Maximum 4 in. wide (AAMA71 or ICC-ES AC 148 complying)
NoteOptional - Spray primer to aid in adhesion of either 1 or 2 applied at a maximum of 5 inches wide
Weather-resistive barrier applied to exterior insulationNone
Exterior Veneer
Part 1
Use either 1, 2, 3, 4, 5, 6, 7, or 8
 
1Brick
-Brick veneer anchors - standard types - installed maximum 24 in. OC vertically on each stud
-Maximum 2 in. air gap between exterior insulation and brick
-Standard nominal 4 in. thick clay brick
2Stucco - Minimum 3/4 in. thick exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes.
3Minimum 2 in. thick limestone or natural stone veneer or minimum 1 1/2 in. thick artificial cast stone veneer. Any standard installation technique can be used.
4Terracotta cladding - Use any terracotta cladding system in which terracotta is minimum 1 1/4 in. thick. Any standard installation technique can be used
5Metal veneer such as steel, aluminum, copper, etc. Any standard installation technique can be used.
6Cement board siding - Any standard installation technique can be used.
7MCM System - Use any Metal Composite Panel that has been successfully tested by the panel manufacturer via NFPA 285 test method. Installation shall be such that the free air cavity behind the MCM shall not exceed 2 7/8 in.
8Aluminum faced, aluminum honeycomb core panels. Any standard installation technique can be used.
Exterior Veneer
Part 2
Use either 1, 2, 3, or 4
 
1Brick
-Brick veneer anchors - standard types - installed maximum 24 in. OC vertically on each stud
-Maximum 2 in. air gap between exterior insulation and brick
-Standard nominal 4 in. thick clay brick
2Stucco - Minimum 3/4 in. thick exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self-adhered membranes.
3Minimum 2 in. thick limestone or natural stone veneer or minimum 1 1/2 in. thick artificial cast stone veneer. Any standard non-open joint installation technique such as ship-lap, etc. can be used.
4Terracotta cladding - Use any terracotta cladding system in which terracotta is minimum 1 1/4 in. thick. Any standard non-open joint installation technique such as ship-lap, etc. can be used.

Note: all barriers to be installed at indicated or recommended application rates and per manufacturer's installation instructions.

For walls containing Atlas EnergyShield® Pro, CGF Pro, Ply Pro or XR exterior insulation
Wall ComponentMaterials
Base Wall System 
Use any of these items
No Sheathing is needed for 1 and 2
 
1Cast concrete walls (1 in. minimum)
2CMU Concrete Walls (1 in. minimum)
320-gauge (minimum) 3 5/8 in. (minimum) steel studs with 5/8 in. thick Type X gypsum wallboard on interior
4Fire-Retardant Treated (FRT) wood studs spaced 24 in. o.c. (maximum) with 5/8 in. thick Type X gypsum wallboard on interior
Floorline Firestopping
Use any of these items
 
1None - only with exterior sheathing option 1, 3, 4, or 5 (gypsum wallboard, concrete, DensElement® or Securock® ExoAir® 430)
24 in. thick, 4-pcf mineral fiber (wool) safing insulation installed with Z-clips or equivalent
31 1/2 in. FRT lumber for use with FRT studs
Cavity Insulation 
Use any of these items
Note: SPF cavity insulations 5-22 must use fire stopping at floor lines and exterior gypsum sheathing (thickness as noted)
 
1None
2Any noncombustible insulation per ASTM E136
3Any mineral fiber (Board Type Class A ASTM E84 faced or unfaced)
4Any fiberglass (Batt Type Class A ASTM E84 faced or unfaced)
55 1/2 in. (maximum) Icynene LD-C-50™ spray foam in 6 in. deep studs (maximum) full fill without an air gap. Use with 5/8 in." exterior sheathing
65 1/2 in. (maximum) Icynene MD-C-200™ 2 pcf spray foam in 6 in. deep studs (maximum) full fill without an air gap. Use with 5/8 in. exterior sheathing.
75 1/2 in. (maximum) Icynene MD-R-210™ 2 pcf spray foam in 6 in. deep studs (maximum) full fill without an air gap. Use with 5/8 in. exterior sheathing.
86 in. (maximum) SWD Urethane QUIK-SHIELD® (QS) 112, 2-pcf spray foam in 6" deep studs (maximum) or partial fill with a maximum 2 1/2 in. air gap. Use with 5/8 in. exterior sheathing.
93 1/2 in. (maximum) Gaco Western 183M spray foam in 3 5/8 in. deep studs (maximum). Use with 5/8 in. exterior gypsum sheathing
103 1/2 in. (maximum) Gaco Western F1850 with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum)
113 5/8 in. (maximum) Demilec Sealection® 500 with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum).
123 5/8 in. (maximum) Demilec HeatLok Soy® 200 Plus with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum)
133 in. (maximum) Bayer Bayseal® with 5/8 in. exterior sheathing
143 in. (maximum) Lapolla Foam-Lok™ FL 2000 with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum)
153 5/8 in. (maximum) BASF SPRAYTITE® 81206 or WALLTITE® (US and US-N) with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum)
163 5/8 in. (maximum) Accella (Premium Spray Products) FoamsulateTM 220 with 5/8 in. exterior sheathing in 3 5/8 in. deep studs (maximum)
173 5/8 in. (maximum) JM Corbond® III or IV - Full stud Cavity depth or less for use with 5/8 in. exterior gypsum sheathing
18BASF WALLTITE® (LWP, Max, XL, Plus) - 3 5/8 in. (maximum). Use with 1/2 in. exterior gypsum sheathing
19Carlisle SealTite™ PRO HFO, SealTite™ PRO Closed Cell, SealTite™ Pro One Zero, SealTite™ Pro Open Cell, SealTite™ Pro High Yield, SealTite™ Pro No Mix, SealTite™ Pro No Trim 21, SealTite™ Pro OCX- 3 5/8 in. (maximum). Use with 1/2 in. exterior gypsum sheathing
20Huntsman HeatLok HFO or HFO Pro - 3 5/8 in. (maximum). Use with 5/8 in. exterior gypsum sheathing
21Holcim Enverge™ EasySeal® 5, Enverge™ SucraSeal - 3 5/8 in. (maximum). Use with 1/2 in. exterior gypsum sheathing
22SWD Urethane (Quick-Shield Goblin or Yeti - 1 in. to 3 5/8 in. thick for use in 3 5/8 in. studs (maximum). Use with 5/8 in. exterior gypsum sheathing)
Exterior Sheathing
Use any of these items
Note: When Items 4 or 5 (integrated sheathing WRB) are used, WRB listed below may not be added on top of the sheathing.
Sheathings 1-7 are only used for stud base walls
No sheathing is needed for Base Walls 1 or 2
 
11/2 in. or thicker exterior type gypsum sheathing
2None - only when cavity SPF insulation is not used and a special opening perimeter is used (see the last entry in this table).
32 in. thick precast concrete panels attached to structural elements of building
41/2 in. or thicker GP DensElement® sheathing with integrated WRB
51/2 in. or 5/8 in. thick USG Securock® ExoAir® 430
67/16 in. (minimum) FRT plywood panels complying with IBC Section 2303.2 and installed following code allowances for Types I, II, III, or IV construction
7NexGen MAXTERRA® MgO 12 mm, 16 mm, or 20 mm
NoteWhen SPF is used in the cavity, exterior sheathing must be used. See specific sheathing thicknesses above
WRB Over Base Wall 
Use any of these items
 
1PERM-A-BARRIER® VPL LT
2PERM-A-BARRIER® NPL 10
3PERM-A-BARRIER® NPL
4PERM-A-BARRIER® NPS
5PERM-A-BARRIER® VPS
6PERM-A-BARRIER® VPL
7PERM-A-BARRIER® Aluminum Wall Membrane (AWM)
8PERM-A-BARRIER® VPL 50RS
9PERM-A-BARRIER® VPS 30
10PERM-A-BARRIER® VPL 50
11PERM-A-BARRIER® Ultra
Z Girts
Use any of these items for claddings requiring girts
 
1Metallic Z Girts
2Horizontal Smart Ci-GreenGirt
3Horizontal Armatherm™ FRR Z Girt
4Knight Wall ThermaZee®
5Strongirt® (Horizontal only) - Claddings must be 8 mm minimum thickness, and not for use with Claddings 7, 8, 10, or 12
6SFS NH3 (horizontal only)
7Cascadia Clip (horizontal only)
NoteGirt spacing should be to comply with wind load per manufacturer instructions.
Exterior Insulation 
Use any of these items 
Items 1, 2, 3, and 4 may be multiple layers of thinner product with faces on each side 
 
14 in. (maximum) Atlas EnergyShield Pro
24 in. (maximum) EnergyShield CGF Pro
34 3/4 in. (maximum) EnergyShield Ply Pro (4 in. EnergyShield CGF Pro with 5/8 in. or 1/4 in. FRT Plywood)
44 in. (maximum) Atlas EnergyShield XR
Note 11/2 in. (minimum) exterior gypsum sheathing may be attached to exterior side of any item listed above. 5/8 in. (min) FRT plywood may be attached to exterior side of Item 1, 2, or 4 listed above
Note 2GP DensGlass® and GP DensElement® (both minimum 1/2 in.) may be installed exterior to items 1, 2, or 4 as listed above
Note 3MgO Board may be installed over the polyiso foam boards. NexGen Max Terra 12mm, 16mm, or 20mm mechanically attached or adhered with construction adhesive 2 in. dabs spaced 18 in. apart or 1 ft. long, 1/4 in. wide ribbons spaced 1 ft. apart.
Note 4The listed sheathing products installed over Items 1, 2, or 4 may only be covered with the WRB products listed to be used over insulation (see WRB list below this section), but are now used over the sheathing covering the insulation unless other are justified via Fire Engineering Evaluation. DensElement® already has a WRB. No WRB goes over this product except the sheathing joint flashing listed in ICC ESR 3786.
Note 5Mineral Wool (unfaced) that meets ASTM E136 as noncombustible may be used over Items 1, 2, 3, or 4. When the mineral wool thickness is 2 in. or greater and density is 4-pcf (minimum), the air gap from the mineral wool surface to the back of the listed claddings is unlimited, except Cladding #7 and #12 are restricted to a 2.25 in. air gap. When the mineral wool is less than 2" thick or 4-pcf density, the air gap form the mineral wool surface to the back of the cladding is restricted to that listed for each Exterior Cladding below.
Note 6See the Special Cladding section of this Table when insulation items 1, 2, or 4, as listed above, are covered with 5/8 in. gypsum sheathing and exterior claddings as listed below are not being used
WRB Over Exterior Insulation
Use any of these items 
 
1PERM-A-BARRIER® Aluminum Wall Membrane (AWM)
2PERM-A-BARRIER® VPL
3PERM-A-BARRIER® VPS
4PERM-A-BARRIER® NPS
5PERM-A-BARRIER® NPL
6PERM-A-BARRIER® VPL LT
7PERM-A-BARRIER® Ultra
Exterior Cladding
Use any of these items
Note: Important: Maximum air gap 2 1/4 in. (distance from cladding inner face to insulation) 
Note: Cladding 8 (zinc) may  only be used with EnergyShield Pro, EnergyShield XR, or EnergyShield Ply Pro.
Note: Diamond Furr TT-4 (manufactured by Brand X Metals) may be used to install 3-coat stucco item 2 in the cladding list.
Cladding may be attached with Knight Wall Systems ThermaZee® or other metallic Z girt
 
1Brick – Nominal 4 in. clay brick or CMU veneer (hollow or solid) with maximum 2 1/4 in. air gap behind the brick or CMU. Brick ties/anchors 24 in. o.c. (maximum)
2Stucco – Minimum 3/4 in. thick exterior cement plaster and lath. An optional secondary WRB (WRB allowed OVER foam over first WRB) can be installed between the insulation and lath. The optional second WRB may be any mechanically attached sheet product, asphalt, or butyl-based building paper (stapled or other mechanical attachment) with no adhesive. The second WRB may not be self-adhering full coverage asphalt or self-adhering full coverage butyl-based membranes. See note for Diamond Furr TT-4 installation. For example, the secondary WRB may be paper backing attached to lath meeting Federal Specification UUB790A: Type 1, Grade D, Style 2, or Fortifiber / Henry Jumbo Tex 60 Minute
3Limestone – Minimum 2 in. thick
4Natural stone veneer – Minimum 2 in. thick
5Cast artificial stone – Minimum 1 1/2 in. thick complying with ICC-ES AC 51
6Terracotta cladding – Minimum 1 1/4 in. thick
7Any ACM or MCM that has passed NFPA 285
8Uninsulated sheet metal building panels including aluminum, steel, copper, or zinc (see Note)
9Uninsulated fiber-cement cladding or siding minimum 1/4 in. thick. Must be 8 mm when Strongirt® is used
10Stone/aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria
11Autoclaved-aerated-concrete (AAC) panels (minimum 1 1/2 in. thick)
12Reynobond® ZCM zinc metal composite panel
13Terreal Zephir® Evolution Rainscreen System (terra cotta), minimum 9/16 in. thick
14User note - reserved for FunderMax m.look cladding with maximum 1 1/2 in. airspace, cladding manufacturer no longer supports use of this cladding in U.S. exterior walls
15CERACLAD using the manufacturer standard installation technique, air gap not to exceed 15mm
16CUPACLAD Slate: 101 Logic, 101 Random, 101 Parallel, 210 Vanguard. Must be 8mm minimum when Strongirt® is used
17Glen-Gery Thin Tech® Masonry Veneer (only with optional noncombustible mortar)
18Glen-Gery Tru-Brix (only with optional noncombustible mortar)
19Telling Corium Thin Brick System (only with steel or aluminum brick tray and optional noncombustible mortar)
20Thin brick or stone (minimum 3/4 in. thick clay brick) fully adhered with cementitious mortar (standard or polymer-modified) to the base wall. A secondary WRB can be installed between the exterior sheathing and the brick. The secondary WRB shall not be full-coverage asphalt or butyl-based self-adhered membranes. See cladding #2 for examples
21Telluride Stone (minimum 1 in.) applied to the base wall (with Atlas approved WRB or WRB in Cladding #20) using plaster/lath
225/8 in. Nichiha Architectural Wall Panels (AWP 3030), Nichiha Cladding 5/16 in. per Intertek CCRR 0258. Nichiha Cladding must be 8mm minimum when Strongirt® is used
23Ceramic or Porcelain Tile. Must be 8mm minimum when Strongirt® is used
a1/4 in. minimum generic Ceramic or Porcelain tile - mechanically attached
bCeramic or Porcelain tile- 3/8 in. thick (minimum) bonded using noncombustible mortar adhesive to a 1/2 in. thick (minimum) cement board or gypsum sheathing
c12 mm Porcelanosa XTone per ESR 4555
24Any one coat stucco (3/8 in. to 1/2 in. min) that meets any of the following:
aAC11 acceptance criteria for one coat stucco; or
bis approved for use in Type I-IV construction; or
chas been tested per NFPA285; or
dstays in place when tested per ASTM E119 (stucco exposed to fire) for at least 30 minutes
25Any noncombustible cement board adhered to the exterior side or mechanically attached to framing through EnergyShield Pro, EnergyShield XR or EnergyShield CGF Pro. The cement board is covered with NFPA 285 approved EIFS lamina (mesh, base coat, and finish coat) WITHOUT the EIFS Expanded Polystyrene (EPS) board. Adhered cement board may be installed over the polyiso with
construction adhesive of 2 in. D dabs spaced 18 in. apart or, 1 ft. long 1/4 in. wide ribbons spaced 1 ft. apart. EIFS Approval Examples: MasterWall (IAPMO ER0433), Dryvit (ESR 1543), STO (ESR 2536), and other accredited 3rd party EIFS approvals.
 
268 mm (min) or 5/16 in. (min) SwissPearl® Fiber Cement Cladding
27Thin Brick with SpeedyMason Brick Lath and Brick Lath Rainscreen - minimum 9/16 in. thick
aMay be used without exterior stud sheathing
bAll screws must penetrate through to studs, with the exception of EnergyShield Ply Pro, where the system can attach directly to the FRT plywood
cMust use Spec Mix Adhered Veneer Thin Veneer Adhesion Mortar XP500 or cementitious mortar (standard or polymer modified)
dMust use header as test
Special Claddings 
Use the base walls listed above. When gypsum sheathing is not used on stud exterior, do not use spray foam in stud cavity. ONLY use WRBs over 5/8 in. gypsum that are explicitly approved together with the Special Claddings
 
1When 5/8 in. gypsum sheathing is used over Atlas polyiso with or without exterior sheathing on the exterior of studs (and the window opening is lined with 5/8 in. gypsum board over 16-gauge steel), the following claddings may be used.
aHigh Pressure Laminate (HPL) exterior veneers are allowed for use when the HPL veneer and the water resistive barrier proposed for use have been successfully tested / approved together per NFPA 285. The installation requirements outbound from the 5/8 in. gypsum layer in the approval report must be followed, including all exterior layers, furring, attachment depth, and maximum air gap behind the cladding. 
bExterior veneers of NFPA 285-compliant combustible materials are allowed for use when the combustible veneer and the WRB contemplated for use have been successfully tested/approved together per NFPA 285. The installation requirements outbound from the 5/8 in. gypsum layer in the approval report must be followed, including all exterior layers, furring, attachment depth, and maximum air gap behind the cladding. As an example, Parklex Prodema Naturclad-B F wood laminate panel system installed over DuPont™ Tyvek® Firecurb HDPE Membrane water-resistive barrier per Intertek Design PUI/CWP 30-05.
Flashing of Opening Perimeter (Windows, Doors, etc.) 
Use items 1, 2, or 3
 
1There is no restriction on flashings of openings for wall designs referencing compliance with NFPA 285-12, when using gypsum sheathing on the exterior of studs or Base Wall 1 or 2.
2For wall designs referencing NFPA 285-23 or older editions of NFPA 285 with gypsum sheathing on the stud exterior, or for Base Wall 1 or 2, use the following: Header 24-gauge Steel w/ 0.040 aluminum surrounding the steel.
3When the Atlas polyiso is directly attached to studs with no sheathing over the exterior side of studs, use 5/8 in. Type X gypsum board on the opening perimeter, and 24-gauge (min) steel flashing shall be used. This meets NFPA 285-23 or older versions of NFPA 285.
NoteException: When the Atlas polyiso is directly attached to studs and is covered with 1/2 in. (minimum) gypsum sheathing, 12 mm (minimum) NexGen MgO, GP DensGlass®, or DensElement®, the 24-gauge steel flashing restriction is waived if the studs are fire stopped at every floor line with mineral wool.

gcpat.com | North America Customer Service: +1 (877) 423 6491

We hope the information here will be helpful. It is based on data and knowledge considered to be true and accurate, and is offered for consideration, investigation and verification by the user, but we do not warrant the results to be obtained. Please read all statements, recommendations, and suggestions in conjunction with our conditions of sale, which apply to all goods supplied by us. No statement, recommendation, or suggestion is intended for any use that would infringe any patent, copyright, or other third party right.

GCP Applied Technologies and PERM-A-BARRIER® are trademarks, which may be registered in the United States and/or other countries, of GCP Applied Technologies Inc. This trademark list has been compiled using available published information as of the publication date and may not accurately reflect current trademark ownership or status.

© Copyright 2021 GCP Applied Technologies Inc. All rights reserved. PAB-126-0221


GCP Applied Technologies, 20 Moores Road, Malvern, PA 19355, USA.
GCP Canada, Inc., 294 Clements Road, West, Ajax, Ontario, Canada L1S 3C6
This document is only current as of the last updated date stated below and is valid only for use in the United States. It is important that you always refer to the currently available information at the URL below to provide the most current product information at the time of use. Additional literature such as Contractor Manuals, Technical Bulletins, Detail Drawings and detailing recommendations and other relevant documents are also available on www.gcpat.com. Information found on other websites must not be relied upon, as they may not be up-to-date or applicable to the conditions in your location and we do not accept any responsibility for their content. If there are any conflicts or if you need more information, please contact GCP Customer Service.

Last Updated: 2026-06-09

https://gcpat.com/en/solutions/products/perm-a-barrier-air-barrier-system/perm-a-barrier-air-barriers-nfpa-compliant